MULTI-PURPOSE CONTROL APPLICATION
Table 61: Digital inputs (Control keypad: Menu M2 -> G2.2.4)
Index
Parameter
P2.2.7.1 *
Start signal 1
P2.2.7.2 *
Start signal 2
P2.2.7.3 *
Run enable
P2.2.7.4 *
Reverse
P2.2.7.5 *
Preset speed 1
P2.2.7.6 *
Preset speed 2
P2.2.7.7 *
Preset speed 3
Motor potentiometer refer-
P2.2.7.8 *
ence DOWN
Motor potentiometer refer-
P2.2.7.9 *
ence UP
P2.2.7.10 *
Fault reset
P2.2.7.11 *
External fault (close)
P2.2.7.12 *
External fault (open)
P2.2.7.13 *
Acc/Dec time selection
P2.2.7.14 *
Acc/Dec prohibit
P2.2.7.15 *
DC braking
P2.2.7.16 *
Jogging speed
P2.2.7.17 *
AI1/AI2 selection
P2.2.7.18 *
Control from I/O terminal
P2.2.7.19 *
Control from keypad
P2.2.7.20 *
Control from fieldbus
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Default
Cust
0.1
A.1
0.1
A.2
0.1
0.2
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
A.3
0.1
A.5
0.1
0.2
0.1
A.6
0.1
0.1
0.1
0.1
0.1
A.4
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
VACON · 153
ID
Description
403
See P2.2.1.1.
404
See P2.2.1.1.
407
Motor start enabled (cc)
Direction forward (oc)
412
Direction reverse (cc)
419
See preset speeds in Basic
Parameters (G2.1).
420
421
Mot.pot. reference decrea-
417
ses (cc).
Mot.pot. reference increases
418
(cc).
Resets all active faults when
414
TRUE.
405
Ext. fault (F51) displayed (cc).
Ext. fault (F51) displayed
406
(oc).
408
Acc/Dec time 1 (oc)
Acc/Dec time 2 (cc)
No acceleration or decelera-
415
tion is possible until the con-
tact is open.
416
DC braking active (cc).
Jogging speed selected for
413
frequency reference (cc).
cc = AI2 is used as reference,
422
when ID117 = 14
Force Control to I/O termi-
409
nal.
410
Force Control to Keypad.
411
Force Control to Fieldbus.
6