PARAMETER DESCRIPTIONS
303 REFERENCE SCALING, MINIMUM VALUE 2346 (2.2.4, 2.2.16, 2.2.2.6)
304 REFERENCE SCALING, MAXIMUM VALUE 2346 (2.2.5, 2.2.17, 2.2.2.7)
Additional reference scaling. If both parameter ID303 and parameter ID304 = 0 scaling is set
off. The minimum and maximum frequencies are used for scaling.
NOTE!
This scaling does not affect the fieldbus reference (scaled between Minimum
frequency (parameter ID101) and Maximum frequency (parameter ID102).
f
out
f
ID102
max
ID304
ID303
f
ID101
min
0
Fig. 34: Left: Reference scaling; Right: No scaling used (parameter ID303 = 0)
305 REFERENCE INVERSION 2 (2.2.6)
Inverts reference signal:
Max. input signal = Min. freq. reference
Min. input signal = Max. freq. reference
Table 118: Selections for parameter ID305
Selection
Selection name
number
0
No inversion
1
Reference inverted
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
f
out
f
ID102
max
AI [V]
f
ID101
min
10
0
VACON · 255