PARAMETER DESCRIPTIONS
Table 190: Selectable wake-up functions
Selection
Function
number
Wake up happens
when actual value
goes below the
limit
2
Wake up happens
when actual value
exceeds the limit
3
1020 PID CONTROLLER BYPASS 7 (2.9.16)
With this parameter, the PID controller can be programmed to be bypassed. Then the
frequency of the controlled drive and the starting points of the auxiliary drives are defined
according to the actual value signal.
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Limit
The limit defined with
parameter ID1018 is in
percent of the current
value of the reference sig-
nal
The limit defined with
parameter ID1018 is in
percent of the current
value of the reference sig-
nal
Description
Actual
value
signal
100%
reference=50%
Par. ID1018=60%
limit=60%*reference=30%
Start
Stop
Actual
value
signal
100%
Par. ID1018=140%
limit=140%*reference=70%
reference=50%
VACON · 343
t
t
Start
Stop
8