Vacon NX series Applications Manual page 278

All in one
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

VACON · 278
Table 137: Selections for parameter ID361
Selection
number
0
Not in use
1
Analogue input 1 (AI1)
2
Analogue input 2 (AI2)
362 FREE ANALOGUE INPUT, FUNCTION 34 (2.2.21, 2.2.18)
This parameter is used for selecting a function for a free analogue input signal:
Table 138: Selections for parameter ID362
Selection
number
0
Function is not in use
Reduces motor current limit
1
(ID107)
Reduces DC braking current
2
Reduces acceleration and
deceleration times
3
Reduces torque supervision
4
limit
Fig. 50: Scaling of max. motor current
8
Selection name
Selection name
This signal will adjust the maximum motor current between
0 and max. limit set with ID107. See Fig. 50.
DC braking current can be reduced with the free analogue
input signal between zero current and the current set with
the parameter ID507. See Fig. 51.
Acceleration and deceleration times can be reduced with the
free analogue input signal according to the following formu-
las: Reduced time = set acc./deceler. time (parameters
ID103, ID104; ID502, ID503) divided by the factor R in Fig. 52.
Set supervision limit can be reduced with the free analogue
input signal between 0 and set torque limit supervision value
(ID349), see Fig. 53.
Torque limit
100%
Par. ID107
0 V
Signal range
0 mA
4 mA
Custom
PARAMETER DESCRIPTIONS
Description
Description
AI
10 V
20 mA
20 mA
Custom
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205