Page 2
Follow the commissioning instructions, see Chapter 10. 10. The Vacon NX_ Frequency Converter is now ready for use. Vacon Plc is not responsible for the use of the frequency converters against the instructions. Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com...
Page 3
2 • vacon CONTENTS VACON NXC USER’S MANUAL INDEX SAFETY INTRODUCTION RECEIPT OF DELIVERY TECHNICAL DATA MOUNTING CABLING AND CONNECTIONS LOW HARMONIC REGENERATIVE CABINET DRIVE INSTALLATION INSTRUCTIONS CONTROL KEYPAD COMMISSIONING FAULT TRACING Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com...
Power ratings ..........................14 4.1.1 Vacon NXP/C – Mains voltage 380—500 V ................14 4.1.2 Vacon NXC Regenerative low harmonic drives – Mains voltage 380—500 V ......15 4.1.3 Vacon NXP/C 6 – Mains voltage 500—690 V ................16 4.1.4 Vacon NXC Regenerative low harmonic drives – Mains voltage 525—690 V ......17 Technical data ..........................
Page 5
4 • vacon 6.2.2 Mains and motor cables......................33 6.2.3 Thermal supervision of option +ODU ..................42 6.2.4 DC supply and brake resistor cables ..................42 6.2.5 Control cable ..........................42 6.2.6 Cable and fuse sizes, 380-500V units ..................43 6.2.7 Cable and fuse sizes, 500/525-690V units .................
Vacon NX is disconnected from mains. Before connecting the frequency converter to mains make sure that the Vacon NX front and cable covers as well as the cabinet doors are closed. Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com...
SAFETY Earthing and earth fault protection The Vacon NX frequency converter must always be earthed with an earthing conductor connected to the PE bar in the lower front side of the cabinet. The earth fault protection inside the frequency converter protects only the converter itself against earth faults in the motor or the motor cable.
• 7 INTRODUCTION The Vacon NXC is a product range of free standing enclosed frequency converters for the high power range. The NXC is a modular product intended for use in all applications where reliability and high availability is appreciated.
8 • vacon INTRODUCTION Manufacturer's declaration of conformity Below you can find the Manufacturer's Declarations of Conformity assuring the compliance of Vacon NXP/C frequency converters with the EMC-directives. EU DECLARATION OF CONFORMITY Manufacturer's name: Vacon Oyj Manufacturer's address: P.O.Box 25...
• 9 RECEIPT OF DELIVERY Vacon NX frequency converters have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (com- pare the type designation of the product to the code below).
10 • vacon RECEIPT OF DELIVERY NXC additional option codes The NXC enclosure solution contains additional pre-engineered hardware options. These options are appended to the basic type code by using “+” codes. You will find the complete type code on the name plate of the unit.
If DC-voltage is not available and the unit has been stored de-energized much longer than 1 year consult factory before connecting power. Maintenance In normal conditions, Vacon NX frequency converters are maintenance-free. However, we recommend to keep the converter clean, e.g. by cleaning the heatsink with compressed air whenever necessary.
(Vacon Warranty Terms). The local distributor may grant a warranty time different from the above. This warranty time shall be specified in the distributor's sales and warranty terms. Vacon assumes no responsibility for any other warranties than that granted by Vacon itself.
FR14 2806X2275X605/2500 Table 4-1. Power ratings and dimensions of Vacon NX 6- and 12-pulse drives supply voltage 380—500V. Note: The rated currents in given ambient temperatures are achieved only when the switching fre- quency is equal to or less than the factory default (automatic thermal management).
1500 1200 2xFI13+FI14 4406X2275X605/3900 Table 4-2. Power ratings and dimensions of Vacon regenerative low-harmonic drives, supply voltage 380—500V Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default (automatic thermal management).
FR14 2806X2275X605/2500 Table 4-3. Power ratings and dimensions of Vacon NX 6- and 12-pulse drives, supply voltage 500—690V. Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default (automatic thermal management).
2xFI13+FI14 2806X2275X605/2500 Table 4-4. Power ratings and dimensions of Vacon regenerative low-harmonic drives, supply voltage 525-690V. Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default (automatic thermal management).
18 • vacon TECHNICAL DATA Technical data Mains Input voltage U 380…500V; 500…690V; –10%…+10% connection 380...500V;525...690V; –10%…+10% (regenerative drives) Input frequency 45…66 Hz Connection to mains Once per minute or less (normal case); Motor Output voltage 0—U connection Continuous output Ambient temperature max.
Page 20
TECHNICAL DATA vacon • 19 EMC (at default Immunity Fulfils all EMC immunity requirements settings) Emissions EMC level L: EN 61800-3 (2004), Category C3 EMC level T: Low earth-current solution for IT- networks, EN 61800-3 (2004), Category C4 (can be...
20 • vacon MOUNTING MOUNTING Dimensions The table below shows the dimensional drawing of the basic cabinet. Please note that certain NXC options will further affect the total width or height of the cabinet. Always refer to the delivery specific information for the exact dimensions.
22 • vacon MOUNTING Lifting the unit out of the transport packaging The unit is delivered either in a wooden box or a wooden cage. The box may be transported either horizontally or vertically, while transportation of the cage in a horizontal position is not allowed.
MOUNTING vacon • 23 5.3.1 Fixing to the floor and to the wall In installations where the cabinet is mounted against the wall, it is more convenient to fix the top of the cabinet to the wall. Fix the cabinet in the two front corners to the floor with bolts. Fix the top part to the wall with bolts.
Note: The NXC regenerative low-harmonic drive incorporates an LCL filter instead of AC chokes and this instruction can be ignored. The AC input choke carries out several functions in the Vacon NX 6- and 12-pulse frequency converter. The input choke is needed as an essential component for motor control, to protect the input and DC-link components against abrupt changes of current and voltage as well as to function as a protection against harmonics.
MOUNTING vacon • 25 Auxiliary voltage transformer tappings Note: An auxiliary voltage transformer is always included as standard in NXC regenerative low- harmonic drives. If the drive is ordered with an auxiliary voltage transformer for 230V auxiliary voltage supply (+ATx option) the tappings of the transformer have to be set according to the mains voltage.
26 • vacon MOUNTING Cooling 5.6.1 Free space around the cabinet Enough space must be left above and in front of the cabinet to ensure sufficient cooling and space for maintenance. The amount of cooling air required is indicated in the table below. Also make sure that the tempera- ture of the cooling air does not exceed the maximum ambient temperature of the converter.
28 • vacon MOUNTING Power losses The power loss of the frequency converter varies greatly with load and output frequency as well as with the switching frequency used. For dimensioning of cooling or ventilation equipment for electri- cal rooms the following generic formula gives a good approximation of the heat losses at nominal...
CABLING AND CONNECTIONS vacon • 29 CABLING AND CONNECTIONS Understanding the power unit topology Figure 6-1 and Figure 6-2 show the principles for mains and motor connections of the basic 6-pulse drive in frame sizes FR10 to FR14. Some units built in frame size FR11 have double input devices and require an even number of supply cables but an uneven number of motor cables can be used.
Page 31
30 • vacon CABLING AND CONNECTIONS FI9-10 FI12 Single Single input input Single Single output output FI14 FI13 Single Double input input Single Double du/dt du/dt output output ud1 011k1 7.fh11 Figure 6-2. Topology of mechanical sizes NXC regenerative low-harmonic drives FI9 – FI14 Note! Some options affect the wiring direction and principle for power cables;...
AFE side. The LCL filter also includes capacitors connected against ground potential. There are resistors connected across the capacitors for discharging these when the LCL filter is disconnected from the input power. Figure 6-3. Vacon LCL filter wiring diagram. 6.2.1.1 Removing HF capacitors If a mains rectifier of another manufacturer is connected to the same input transformer, the capacitors must be removed.
CABLING AND CONNECTIONS vacon • 33 6.2.2 Mains and motor cables The mains cables are connected to terminals L1, L2 and L3 (12-pulse units 1L1, 1L2, 1L3, 2L1, 2L2, 2L3) and the motor cables to terminals marked with U, V and W, see Figure 6-7.
Page 35
Tables 6-2 and show the minimum dimensions of Cu- and Al-cables and the recommended aR fuse sizes. If the motor temperature protection of the drive (see Vacon All in One Application Manual) is used as an overload protection, the cable should be chosen accordingly. If three or more cables are used parallelly (per block) in bigger units each cable requires a separate overload protection.
Page 36
CABLING AND CONNECTIONS vacon • 35 Conn ect motor cables to terminals U, V and W on converter using cable lugs Connect mains cables to terminals L1, L2 and L3 on the input device (if used) or to power terminals on...
Page 37
36 • vacon CABLING AND CONNECTIONS Connect mains cables to terminals L1, L2 and L3 (behind the plexiglass) on the converter Connect motor cables to terminals U, V and W on converter Connect the PE Connect the PE conductors to the PE bar conductors to the PE bar Figure 6-9.
Page 38
CABLING AND CONNECTIONS vacon • 37 Connect motor cables to terminals U, V and W Connect mains cables on converter to terminals L1, L2 and L3 on the AC drive Connect the PE conductor to the PE bar Figure 6-11. Routing of power cables, bottom cabling, frame Fi12 +ODU (optional)
Page 39
38 • vacon CABLING AND CONNECTIONS Figure 6-13. Routing of power cables, bottom cabling, frame Fi14 6.2.2.1 Routing of power cables through bottom of cabinet Route the supply and motor cables through the cabinet bottom as shown in Figure 6-14. To conform to the EMC requirements, a particular cable gland shall be used.
Page 40
CABLING AND CONNECTIONS vacon • 39 Cable tie Fastening spring Metal sock PE(N) screen Assembly plate Cable Bush ring Rubber sealing ud1011k11.fh11 Figure 6-15. Components of the cable gland set Installing the cable gland Unless the cable gland is already installed by the manufacturer, follow the procedure below to do this: Assemble the rubber sealing in the narrow groove of the bush ring.
Page 42
Vacon's delivery consists of fixed sets of ferrite rings (option). When ferrite rings are used to attenuate the risk of bearing damages, use always two ferrite ring sets per motor cable.
6.2.4 DC supply and brake resistor cables Vacon 6- and 12-pulse frequency converters can optionally be equipped with terminals for DC supply and with an external brake resistor. These terminals are marked with B-, B+/R+ and R-. The DC bus connection is made to terminals B–...
Even Al: 8*(3*300+88Cu) Table 6-2. Cable and fuse sizes for Vacon NX_5, 6-pulse supply Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each other. Ambient temperature is 30°C (86°F). EN60204-1 and IEC 60364-5-523.
Page 45
Even Al: 8*(3*300Al+88Cu) Table 6-3. Cable and fuse sizes for Vacon NX_5, 12-pulse supply Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each other. Ambient temperature is 30°C (86°F). EN60204-1 and IEC 60364-5-523.
Page 46
Even Al: 8*(3*300+88Cu) Table 6-4. Cable and aR fuse sizes for Vacon NX_5 Regenerative low-harmonic drive. Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each other. Ambient temperature is 30°C (86°F). EN60204-1 and IEC 60364-5-523.
Even Al:8*(3*300+88Cu) Table 6-5. Cable and aR fuse sizes for Vacon NX_6, 6-pulse supply Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each other. Ambient temperature is 30°C (86°F). EN60204-1 and IEC 60364-5-523.
Page 48
Even Al:8*(3*300+88Cu) Table 6-6. Cable and aR fuse sizes for Vacon NX_6, 12-pulse supply Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each other. Ambient temperature is 30°C (86°F). EN60204-1 and IEC 60364-5-523.
Page 49
Even Even Al:8*(3*300+88Cu) Cable and aR fuse sizes for Vacon NX_6 Regenerative low-harmonic drive. 6-7. Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each other. Ambient temperature is 30°C (86°F). EN60204-1 and IEC 60364-5-523.
LOW HARMONIC REGENERATIVE CABINET DRIVE vacon • 49 LOW HARMONIC REGENERATIVE CABINET DRIVE This chapter describes the functionalities of control devices (switches, push-buttons and LED lamps) of the NXC low-harmonic regenerative drive (mechanical units FI9-14). The functionalities of additional “+”...
50 • vacon LOW HARMONIC REGENERATIVE CABINET DRIVE Turning the switch –S10 into position 0 will open the circuit-breaker if it is closed or stop the possible ongoing pre-charging regardless of the selected control place/manner. Turning the switch into position 1 enables the pre-charging and the circuit-breaker to be controlled by the selected mode of the REM-MAN-AUTO selector switch.
LOW HARMONIC REGENERATIVE CABINET DRIVE vacon • 51 Figure 7-4. Circuit diagram of remote contacts for the control of the MCCB and pre-charging circuit (NXC regenerative low-harmonic FR12) In case of a voltage drop of <0.7xU or a blackout in the supplying network, the undervoltage release coil will open the circuit-breaker and pre-charging and MCCB closing has to be activated by the remote charging pulse when the supply is energized.
Page 53
52 • vacon LOW HARMONIC REGENERATIVE CABINET DRIVE In case of an overcurrent situation the fault that caused the circuit-breaker to trip should be identified and removed before the circuit-breakers can be reset. The MCCB can only be reset by pressing the push button -S6 when the –S11 REM-MAN-AUTO switch is in MAN position.
INSTALLATION INSTRUCTIONS vacon • 53 INSTALLATION INSTRUCTIONS Before starting the installation, check that none of the components of the frequency converter is live. Make sure that the space where the converter is installed, and the con- verter itself, is clean and free from particles, dust or humidity that could harm the converter when it is powered on.
54 • vacon INSTALLATION INSTRUCTIONS Connect the cables: Strip the motor and mains cables Remove the protection grids for the input terminals and the protection covers on the converter module(s). Pull the cable through the bottom plate and fix the PE conductor to the PE bar of the cabinet.
INSTALLATION INSTRUCTIONS vacon • 55 8.1.1 Cable and motor insulation checks 1. Motor cable insulation checks Disconnect the motor cable from terminals U, V and W of the frequency converter and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor.
The I/O boards mounted at the factory are indicated in the type code. For more information on the option boards, see Vacon NX option board manual (ud741). The control board can be powered externally (+24V, ±10%) by connecting the external power source to either of the bidirectional terminala #6 or #12, see page 59.
INSTALLATION INSTRUCTIONS vacon • 57 8.2.1 Control connections The basic control connections for boards A1 and A2/A3 are shown in Chapter 8.2.2. The signal descriptions are presented in the All in One Application Manual. +10Vref Reference AI1+ (voltage) AI2+ Reference...
Page 59
58 • vacon INSTALLATION INSTRUCTIONS 8.2.1.1 Control cables The control cables shall be at least 0.5 mm screened multicore cables, see Table 6-1. The maximum terminal wire size is 2.5 mm for the relay terminals and 1.5 mm for other terminals.
INSTALLATION INSTRUCTIONS vacon • 59 8.2.2 Control terminal signals OPT-A1 Terminal Signal Technical information +10 Vref Reference voltage Maximum current 10 mA AI1+ Analogue input, Selection V or mA with jumper block X1 (see page 62): voltage or current Default: 0– +10V (Ri = 200 k ) (-10V…..+10V Joy-stick control, selected with a jumper)
Page 62
INSTALLATION INSTRUCTIONS vacon • 61 8.2.2.2 Jumper selections on the OPT-A1 basic board The user is able to customise the functions of the frequency converter to better suit his needs by selecting certain positions for the jumpers on the OPT-A1 board. The positions of the jumpers determine the signal type of analogue and digital inputs.
Page 63
62 • vacon INSTALLATION INSTRUCTIONS Jum per block X 1 : Jum per block X 2 : AI1 m ode AI2 m ode AI1 mode: 0...20mA; Current input AI2 mode: 0...20mA; Current input AI1 mode: Voltage input; 0...10V AI2 mode: Voltage input; 0...10V AI1 mode: Voltage input;...
INSTALLATION INSTRUCTIONS vacon • 63 Connecting power supply and internal control cables You might need to establish the fibre cable connections from the star coupler board to the power module. Connect the cables according to Figure 8-11. The control unit uses 24 VDC supplied from the ASIC board, which is located on the left side of the power unit 1.
64 • vacon INSTALLATION INSTRUCTIONS Optic fibre cables, signal listing and connections Star coupler board on control unit Terminals on ASIC board of power module 1 Trip signal from power module 1 Gate control enable VaconBus data from ASIC 1 to control board...
• 65 CONTROL KEYPAD The control keypad is the link between the Vacon frequency converter and the user. The Vacon NX control keypad features an alphanumeric display with seven indicators for the Run status (RUN, , READY, STOP, ALARM, FAULT) and three indicators for the control place (I/O term/ Keypad/BusComm).
66 • vacon CONTROL KEYPAD 9.1.2 Control place indications The symbols I/O term, Keypad and Bus/Comm (see Figure 9-1) indicate the choice of control place made in the Keypad control menu (M3) (see chapter 9.3.3). I/O term = I/O terminals are the selected control place; i.e. START/STOP commands or reference values etc.
CONTROL KEYPAD vacon • 67 Keypad push-buttons The Vacon alphanumeric control keypad features 9 push-buttons that are used for the control of the frequency converter (and motor), parameter setting and value monitoring. Figure 9-2. Keypad push-buttons 9.2.1 Button descriptions This button is used to reset active faults (see Chapter 9.3.4).
68 • vacon CONTROL KEYPAD Navigation on the control keypad The data on the control keypad are arranged in menus and submenus. The menus are used for example for the display and editing of measurement and control signals, parameter settings (chapter 9.3.2), reference values and fault displays (chapter 9.3.4).
Page 70
CONTROL KEYPAD vacon • 69 READY R EADY R EADY I/Oterm I/Ote rm I/Oterm Expander boards A:NXOPTA1 Parameters G1 G5 G1 G1 P1 P3 STOP READY STOP R EADY Change I/Oterm I/Ote rm enter value System Menu Language S1 S9...
70 • vacon CONTROL KEYPAD 9.3.1 Monitoring menu (M1) Menu button right You can enter the Monitoring menu from the Main menu by pushing the when the location indication M1 is visible on the first line of the display. How to browse through the monitored values is presented in Figure 9-4.
CONTROL KEYPAD vacon • 71 9.3.2 Parameter menu (M2) Parameters are the way of conveying the commands of the user to the frequency converter. The parameter values can be edited by entering the Parameter Menu from the Main Menu when the location indication M2 is visible on the first line of the display.
Page 73
72 • vacon CONTROL KEYPAD Keypa d Input signals READY READY READY Ke ypad Ke ypad Keypad Parameters Basic parameters Min Frequency P1 P18 G1 G8 13.95 Hz READY READY Keypad Keypad Min Frequency Min Frequency 13.95 Hz enter 14.45 Hz Figure 9-5.
CONTROL KEYPAD vacon • 73 9.3.3 Keypad control menu (M3) In the Keypad Controls Menu , you can choose the control place, edit the frequency reference and Menu button right change the direction of the motor. Enter the submenu level with the...
Page 75
74 • vacon CONTROL KEYPAD 9.3.3.2 Keypad reference The keypad reference submenu (P3.2) displays and allows the operator to edit the frequency reference. The changes will take place immediately. This reference value will not, however, influence the rotation speed of the motor unless the keypad has been selected as source of reference.
CONTROL KEYPAD vacon • 75 9.3.4 Active faults menu (M4) The Active faults menu can be entered from the Main menu by pushing the Menu button right when the location indication M4 is visible on the first line of the keypad display.
Page 77
76 • vacon CONTROL KEYPAD Fault type symbol Meaning This type of fault is a sign of an unusual operating (Alarm) condition. It does not cause the drive to stop, nor does it require any special actions. The 'A fault' remains in the display for about 30 seconds.
CONTROL KEYPAD vacon • 77 9.3.5 Fault history menu (M5) The Fault history menu can be entered from the Main menu by pushing the Menu button right when the location indication M5 is visible on the first line of the keypad display. Find the fault codes in Table 11-2.
78 • vacon CONTROL KEYPAD 9.3.6 System menu (M6) The System menu can be entered from the main menu by pushing the Menu button right when the location indication M6 is visible on the display. The controls associated with the general use of the frequency converter, such as application selection, customised parameter sets or information about the hardware and software are located under the System menu .
Page 80
CONTROL KEYPAD vacon • 79 HMI acknowledg. P6.7.3 5000 timeout HMI number of P6.7.4 retries System S6.8 information S6.8.1 Total counters C6.8.1.1 MWh counter Power On day C6.8.1.2 counter Power On hours C6.8.1.3 hh:mm:ss counter S6.8.2 Trip counters T6.8.2.1 MWh counter Clear T6.8.2.2...
Page 81
9.3.6.1 Language selection The Vacon control keypad offers you the possibility to control the frequency converter through the keypad in the language of your choice. Locate the language selection page under the System menu . Its location indication is S6.1. Press the Menu button right once to enter the edit mode.
Page 82
The parameter copy menu (S6.3) embodies four functions: Parameter sets (S6.3.1) The Vacon NX frequency converter features a possibility for the user to load back the factory default parameter values and to store and load two customised parameter sets (all parameters included in the application).
Page 83
82 • vacon CONTROL KEYPAD READY READY enter CONFIRM Parameter sets Parameter sets Select LoadFactDef CANCEL READY READY Parameter sets Parameter sets Wait... Figure 9-11. Storing and loading of parameter sets Upload parameters to keypad (To keypad, S6.3.2) This function uploads all existing parameter groups to the keypad provided that the drive is stopped.
Page 84
. Choose Yes or No with the Browser buttons pressing the When the Parameter backup function is activated Vacon NX control keypad makes a copy of the parameters of the presently used application. Every time a parameter is changed the keypad backup is automatically updated.
Page 85
84 • vacon CONTROL KEYPAD READY READY Set1 ParamComparison C1 C3 READY READY Set1 P2.1.2= 50.0 P1 P6 20.0 Hz READY EDIT VALUE P2.1.2= 50.0 20.0 Hz CONFIRM CHANGE enter Figure 9-13. Parameter comparison 9.3.6.5 Security NOTE: The Security submenu is protected with a password. Store the password in a safe place! Password (S6.5.1)
Page 86
CONTROL KEYPAD vacon • 85 Parameter lock (P6.5.2) This function allows the user to prohibit changes to the parameters. If the parameter lock is activated the text *locked* will appear on the display if you try to edit a parameter value.
Page 87
CONTROL KEYPAD Multimonitoring items (P6.5.4) Vacon alpha-numeric keypad features a display where you can monitor even three actual values at the same time (see chapter 9.3.1 and chapter Monitoring values in the manual of the application you are using). On page P6.5.4 of the System Menu you can define if it is possible for the operator to replace the values monitored with other values.
Page 88
CONTROL KEYPAD vacon • 87 Default page in the operating menu (P6.6.2) Here you can set the location (page) in the Operating menu (in special applications only) to which the display automatically moves as the set Timeout time (see below) has expired or as the power is switched on to the keypad.
Page 89
88 • vacon CONTROL KEYPAD Note! The brake resistor is available as optional equipment for all classes. It can be installed internally in classes FR4 to FR6. READY READY READY I/Oterm I/Ot erm I/Oterm HW settings InternBrakeRes System Menu P1 P4...
Page 90
CONTROL KEYPAD vacon • 89 Example: Transfer delay between the frequency converter and the PC = 600 ms The value of par. 6.7.3 is set to 1200 ms (2 x 600, sending delay + receiving delay) The corresponding setting shall be entered in the Misc -part of the file NCDrive.ini:...
Page 91
90 • vacon CONTROL KEYPAD Trip counters (S6.8.2) Trip counters (menu S6.8.2) are counters the values of which can be reset i.e. restored to zero. You have the following resettable counters at your disposal. See Table 9-6 for examples. Note! The trip counters run only when the motor is running.
Page 92
CONTROL KEYPAD vacon • 91 Applications (S6.8.4) At location S6.8.4 you can find the Applications submenu containing information about not only the application currently in use but also all other applications loaded into the frequency converter. The information available is:...
Page 93
92 • vacon CONTROL KEYPAD For more information on the expander board-related parameters, see Chapter 9.3.7. I/Oterm I/Oterm Software version B:NXOPTA2 E1 E2 10001.0 READY READY READY I/Oterm I/Oterm I/Oterm Expander boards A:NXOPTA1 State E1 E5 E1 E2 Figure 9-26. Expander board information menus Debug menu (S6.8.7)
Figure 9-27. Expander board information menu Further keypad functions The Vacon NX control keypad embodies additional application-related functions. See Vacon NX Application Package for more information. Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com...
The motor terminals U, V, W and the DC-link/brake resistor terminals –/+ are live when Vacon NX is connected to mains, even if the motor is not running. The control I/O-terminals are isolated from the mains potential. How- ever, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when Vacon NX is disconnected from mains.
Page 96
COMMISSIONING vacon • 95 Set the parameters of group 1 (See Vacon All in One Application Manual) according to the requirements of your application. At least the following parameters should be set: motor nominal voltage motor nominal frequency motor nominal speed motor nominal current You will find the values needed for the parameters on the motor rating plate.
Page 97
96 • vacon Connect the motor to the process (if the startup test was run without the motor being connected) a) Before running the tests, make sure that this can be done safely. b) Inform your co-workers of the tests.
FAULT TRACING vacon • 97 FAULT TRACING The fault codes, their causes and correcting actions are presented in Table 11-2 below. The converter has an internal memory for storing the converter status at the time of fault as well as additional information about the source of the fault.
Time hh:mm:ss, Note: When contacting your Vacon partner because of a fault condition, always write down all texts and codes on the keypad display before. 11.2 Fault codes The fault codes, their causes and correcting actions are presented in the table below. The shadowed faults are A faults only.
Page 100
FAULT TRACING vacon • 99 System fault component failure Reset the fault and restart. faulty operation Should the fault re-occur, contact your Note exceptional fault data record local distributor. Subcode in T.14: S1 = Feedback of motor voltage S2 = Reserved...
Page 101
100 • vacon FAULT TRACING Unbalance Unbalance between power modules in Should the fault re-occur, contact your (Warning only) paralleled units. local distributor. Subcode in T.14: S1 = Current unbalance S2 = DC-Voltage unbalance EEPROM Parameter save fault Should the fault re-occur, contact your...
Page 102
Vacon distributor. Slot fault Defective option board or slot Check board and slot. Contact the nearest Vacon distributor. PT100 board Temperature limit values set for the Find the cause of temperature rise temp. fault PT100 board parameters have been exceeded Table 11-2.
Need help?
Do you have a question about the NXP Series and is the answer not in the manual?
Questions and answers