PID CONTROL APPLICATION
Table 36: Input signals, G2.2
Index
Parameter
P2.2.16
AI1 signal range
AI1 custom mini-
P2.2.17
mum setting
AI1 custom maxi-
P2.2.18
mum setting
P2.2.19
AI1 inversion
P2.2.20
AI1 filter time
AI2 signal selec-
P2.2.21
tion
P2.2.22
AI2 signal range
AI2 custom mini-
P2.2.23
mum setting
AI2 custom maxi-
P2.2.24
mum setting
P2.2.25
AI2 inversion
P2.2.26
AI2 filter time
Motor potentiom-
P2.2.27
eter ramp time
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0
2
–160.00
160.00
%
–160.00
160.00
%
0
1
0.00
10.00
s
0.1
E.10
0
2
-160.00
160.00
%
-160.00
160.00
%
0
1
0.00
10.00
s
0.1
2000.0
Hz/s
Default
Cust
ID
0
320
0.00
321
100.0
322
0
323
0.10
324
A.2
388
1
325
0.00
326
0.00
327
0
328
0.10
329
10.0
331
VACON · 107
Description
0 = 0—10 V (0—20
mA*)
1 = 2—10 V (4 – 20
mA*)
2 = Custom range*
0 = Not inverted
1 = Inverted
0 = No filtering
0 = 0—20 mA (0—
10 V *)
1 = 4 – 20 mA (2—
10 V *)
2 = Custom range*
0 = 0—20 mA*
1 = 4—20 mA*
2 = Customised*
0 = Not inverted
1 = Inverted
0 = No filtering