VACON · 302
502 ACCELERATION TIME 2 234567 (2.4.3)
503 DECELERATION TIME 2 234567 (2.4.4)
These values correspond to the time required for the output frequency to accelerate from the
zero frequency to the set maximum frequency (parameter ID102). These parameters give the
possibility to set two different acceleration/ deceleration time sets for one application. The
active set can be selected with the programmable signal DIN3 (parameter ID301).
504 BRAKE CHOPPER 234567 (2.4.5)
Table 151: Selections for parameter ID504
Selection
number
0
No brake chopper used
Brake chopper in use and tes-
1
ted when running.
External brake chopper (no
2
testing)
Used and tested in READY state
3
and when running
4
Used when running (no testing)
When the AC drive is decelerating the motor, the inertia of the motor and the load are fed
into an external brake resistor. This enables the AC drive to decelerate the load with a torque
equal to that of acceleration (provided that the correct brake resistor has been selected).
The brake chopper test mode generates a pulse to the resistor every second. If the pulse
feedback is wrong (resistor or chopper is missing) fault F12 is generated.
See separate Brake resistor installation manual.
8
Selection name
Can be tested also in READY state.
PARAMETER DESCRIPTIONS
Description
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxp seriesNxs series

Table of Contents