VACON · 264
Table 124: Selections for parameter ID319
Selection
Selection name
number
External fault,
1
normally open
External fault,
2
normally closed
Run enable
3
Acceleration or
deceleration time
4
selection
5
Closing contact
6
Closing contact
Closing contact
7
Reverse
8
Jogging speed
9
(see par. ID124)
10
Fault reset
Acceleration/
11
Deceleration pro-
hibited
DC-braking com-
mand
12
8
Description
Contact closed: Fault is displayed and motor
stopped when the input is active
Contact open: Fault is displayed and motor
stopped when the input is not active.
Contact open, Start of motor disabled.
Contact closed: Start of motor enabled
Contact open, Acceleration/Deceleration time
1 selected
Contact closed: Acceleration/Deceleration
time 2 selected
Force control place to I/O terminal
Force control place to keypad
Force control place to fieldbus
Contact open:Forward
Contact closed:Reverse
Contact closed: Jogging speed selected for
frequency reference
Contact closed: Resets all faults
Contact closed: No acceleration or decelera-
tion possible until the contact is opened
Contact closed: In Stop mode, the DC braking
operates until the contact is opened. See Fig.
41 DC braking command (selection 12) selected
for DIN2
PARAMETER DESCRIPTIONS
Notes
When the control place is
forced to change the values
of Start/Stop, Direction and
Reference valid in the
respective control place are
used (reference according to
parameters ID343, ID121 and
ID122).
NOTE!
The value of ID125 (Keypad
Control Place) does not
change.
When DIN2 opens the control
place is selected according
to keypad control place
selection.
If several inputs are pro-
grammed to reverse, one
active contact is enough to
set the direction to reverse.