Table 54: Basic parameters G2.1
Index
Parameter
Nominal current
P2.1.9 *
of the motor
P2.1.10
Motor cos phi
P2.1.11
I/O reference
Keypad control
P2.1.12
reference
Fieldbus control
P2.1.13
reference
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
Varies
Varies
A
0.30
1.00
0
15/16
0
9
0
9
Default
Cust
ID
5.40
113
0.85
120
0
117
8
121
9
122
VACON · 143
Description
Find the value In
on the rating plate
of the motor.
Find the value on
the rating plate of
the motor.
0 = AI1
1 = AI2
2 = AI1+AI2
3 = AI1-AI2
4 = AI2-AI1
5 = AI1xAI2
6 = AI1 Joystick
7 = AI2 Joystick
8 = Keypad
9 = Fieldbus
10 = Motor poten-
tiometer
11 = AI1, AI2 mini-
mum
12 = AI1, AI2 maxi-
mum
13 = Max fre-
quency
14 = AI1/AI2 selec-
tion
15 = Encoder 1
16 = Encoder 2
(NXP only)
Select the fre-
quency reference
input when the
control place is
Panel.
0 = AI1
1 = AI2
2 = AI1+AI2
3 = AI1-AI2
4 = AI2-AI1
5 = AI1xAI2
6 = AI1 Joystick
7 = AI2 Joystick
8 = Keypad
9 = Fieldbus
See P2.1.12