1316 BRAKE FAULT RESPONSE 6 (2.7.28)
Defines the action when a brake fault is detected.
Table 204: Selections for parameter ID1316
Selection
number
0
No response
1
Warning
Fault, stop mode after fault
2
according to ID506
Fault, stop mode after fault
3
always by coasting
1317 BRAKE FAULT DELAYS 6 (2.7.29)
The delay before the brake fault (F58) is activated. Used when there is a mechanical delay in
the brake. See parameter ID1210.
1324 MASTER/FOLLOWER SELECTION 6 (2.11.1)
Select Master/Follower mode. When the value Follower is selected the Run Request
command is monitored from Master. All other references are selectable by parameters.
Table 205: Selections for parameter ID1324
Selection
number
0
Single Drive
1
Master
2
Follower
1352 SYSTEMBUS FAULT DELAY 6 (2.7.31)
Defines the delays for the fault generation when heartbeat is missing.
1355 TO 1369 FLUX 10-150% 6 (2.6.25.1 - 2.6.25.15)
Motor voltage corresponding to 10%-150% of flux as a percentage of nominal flux voltage.
1385 ID BIT FREE DO2 6 (P2.3.2.6)
Select the signal for controlling the DO. The parameter has to be set in format xxxx.yy where
xxxx is the ID number of a signal and yy is the bit number. For example, the value for DO
control is 43.06. 43 is the ID number of Status Word. So the digital output is ON when bit
number 06 of Status Word (ID no. 43) i.e. Run Enable is on.