Fig. 70: Example of prohibit frequency area setting
515 DC BRAKING FREQUENCY AT STOP 234567 (2.4.10)
The output frequency at which the DC braking starts. See Fig. 70 Example of prohibit
frequency area setting.
516 DC-BRAKING TIME AT START 234567 (2.4.11)
DC-brake is activated when the start command is given. This parameter gives the time
during which the DC current is fed to the motor before the acceleration starts.
DC brake current is used at start in order to premagnetize the motor before running. This
will improve the torque performance at start. Varying between 100 ms to 3 s, the time
needed depends on motor size. A bigger motor requires a longer time. See parameter ID507.
NOTE!
When Flying Start (see parameter ID505) is used as start function DC braking at
start is disabled.
518 ACCELERATION/DECELERATION RAMP SPEED SCALING RATIO BETWEEN PROHIBIT
FREQUENCY LIMITS 23457 (2.5.3, 2.5.7)
Defines the acceleration/deceleration time when the output frequency is between the
selected prohibit frequency range limits (parameters ID509 to ID514). The ramping speed
(selected acceleration/ deceleration time 1 or 2) is multiplied with this factor. E.g. value 0.1
makes the acceleration time 10 times shorter than outside the prohibit frequency range
limits.
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Actual Reference
High Lim
Low Lim
ID509
ID511
ID513
Low
Lim
ID510
ID512
ID514
High
Requested
Lim
Reference
VACON · 307
8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxp seriesNxs series

Table of Contents