Vacon NX series Applications Manual page 300

All in one
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

VACON · 300
Fig. 66: An example of adjust input
494 ADJUST MINIMUM 6 (2.2.1.5)
495 ADJUST MAXIMUM 6 (2.2.1.6)
These parameters define the minimum and maximum of adjusted signals. See Fig. 66 An
example of adjust input.
NOTE!
The adjustment is made to the basic reference signal.
496 PARAMETER SET 1/SET 2 SELECTION * 6 (2.2.7.21)
This parameter defines the digital input, which can be used to select between Parameter Set
1 and Set 2. The input for this function can be selected from any slot. The procedure of
selecting between the sets is explained in the product's User Manual.
Digital input = FALSE:
Set 1 is loaded as the active set
-
Digital input = TRUE:
Set 2 is loaded as the active set
-
NOTE!
The parameter values are stored only when selecting P6.3.1 Parameter sets Store
Set 1 or Store Set 2 in System menu or from NCDrive: Drive > Parameter Sets.
8
f/Hz
Adjusted
Adjust maximum
ID495 = 10%
44 Hz
40 Hz
36 Hz
PARAMETER DESCRIPTIONS
Adjust 0%
Adjust minimum
ID494 = 10%
AI