Vacon NX series Applications Manual page 364

All in one
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

VACON · 364
NOTE!
This function is not available when flying start is selected for start function (ID505).
The parameter is available for NXP drives only.
1536 FOLLOWER FAULT 6 (2.11.8)
Defines the response in Master drive when a fault occurs in any of the follower drives. For
diagnostic purposes, when one of the drives trips to fault the master drive will send a
command to trigger Data Logger in all the drives.
Table 207: Selections for parameter ID1536
Selection
number
0
No response
1
Warning
Fault, stop mode after fault
2
according to Stop function
1550 FLUX CIRCLE STABILATOR GAIN 6 (2.6.26.5)
Gain for flux circle stabilizer (0-32766)
1551 FLUX STABILATOR TC 6 (2.6.26.6)
Filter coefficient of id-current stabilizer.
1552 VOLTAGE STABILATOR TC 6 (2.6.26.11)
Damping rate of voltage stabilizer, (0-1000).
1553 VOLTAGE STABILATOR LIMIT 6 (2.6.26.11)
This parameter sets the limits for the voltage stabilizer output i.e. the max. and the min.
value for the correction term df in FreqScale.
1587 INV DELAYED DO1 6 (P2.3.1.5)
Inverts delayed digital output signal 1.
1588 INV DELAYED DO2 6 (P2.3.2.5)
Inverts delayed digital output signal 2.
1720 TORQUE STABILATOR LIMIT RATIO 6 (2.6.26.4)
Limit of torque stabilator output.
ID111 * ID1720 = Torque Stabilator Limit
8
Selection name
PARAMETER DESCRIPTIONS
Description
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxp seriesNxs series

Table of Contents