Vacon NX series Applications Manual page 204

All in one
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

VACON · 204
Table 85: Basic parameters G2.1
Index
Parameter
P2.1.10 *
Motor cos phi
PID controller ref-
P2.1.11 *
erence signal
(Place A)
PID controller
P2.1.12
gain
PID controller I-
P2.1.13
time
PID controller D-
P2.1.14
time
P2.1.15
Sleep frequency
7
Min
Max
Unit
0.30
1.00
0
6
0.0
1000.0
%
0.00
320.00
s
0.00
10.00
s
0
P2.1.2
Hz
PUMP AND FAN CONTROL APPLICATION
Default
Cust
ID
0.85
120
4
332
100.0
118
1.00
119
0.00
132
10.00
1016
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Description
Find the value on
the rating plate of
the motor.
0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = PID ref from
Keypad control
page, P3.4
5 = PID ref. from
fieldbus (FBPro-
cessDataIN1)
6 = Motor potenti-
ometer
If the value of the
parameter is set to
100%, a change of
10% in the error
value causes the
controller output
to change by 10%.
If this parameter is
set to 1.00 s, a
change of 10% in
the error value
causes the con-
troller output to
change by
10.00%/s.
If this parameter is
set to 1.00 s, a
change of 10% in
the error value
during 1.00 s cau-
ses the controller
output to change
by 10.00%.
The drive goes to
sleep mode when
the output fre-
quency stays below
this limit for a lon-
ger time than set
by Sleep Delay.