MULTI-PURPOSE CONTROL APPLICATION
Table 65: Limit settings (Control keypad: Menu M2 -> G2.3.4)
Index
Parameter
External brake-off
P2.3.4.9
delay
External brake-on
P2.3.4.10
delay
Temperature limit
P2.3.4.11
supervision
Temperature
P2.3.4.12
supervised value
Analogue supervi-
P2.3.4.13
sion signal
Analogue supervi-
P2.3.4.14
sion low limit
Analogue supervi-
P2.3.4.15
sion high limit
NXP drives only
Brake On/Off Cur-
P2.3.4.16
rent Limit
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0.0
100.0
s
0.0
100.0
s
0
2
-10
100
°C
0
4
0.00
100.00
%
0.00
100.00
%
0
2 x I
A
H
Default
Cust
ID
0.5
352
1.5
353
0
354
40
355
0
356
10.00
357
90.00
358
0
1085
VACON · 161
Description
From brake-off
limits.
From Run request.
Use time longer
than P2.1.4.
0 = No supervision
1 = Low limit
2 = High limit
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
DO Off limit. See
P2.3.3.22.
DO Off limit. See
P2.3.3.22.
Brake is closed
and kept closed if
current is below
this value.
6