PUMP AND FAN CONTROL APPLICATION
Table 87: Analogue input 1 (Control keypad: Menu M2 -> G2.2.2)
Index
Parameter
P2.2.2.1
AI1 signal selec-
**
tion
P2.2.2.2
AI1 filter time
P2.2.2.3
AI1 signal range
AI1 custom mini-
P2.2.2.4
mum setting
AI1 custom maxi-
P2.2.2.5
mum setting
AI1 signal inver-
P2.2.2.6
sion
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle)
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0.1
E.10
0.00
10.00
s
0
2
-160.00
160.00
%
-160.00
160.00
%
0
1
Default
Cust
ID
A.1
377
0.10
324
0
320
0.00
321
100.00
322
0
323
VACON · 209
Description
TTF programming.
See Chapter 8.9
"Terminal to func-
tion" (TTF) pro-
gramming principle.
0 = No filtering
0 = 0-10 V (0-20
mA*)
1 = 2-10 V (4-20
mA*)
2 = Customised *
0 = Not inverted
1 = Inverted
7