PARAMETER DESCRIPTIONS
NOTE!
The use of TTF-programming method in the Multi-purpose Control Application.
Because all digital inputs are programmable you first have to assign two DINs for
the Preset Speed functions (parameters ID419 and ID420).
Table 104: Preset speed
Speed
Preset speed 1 (DIN4/ID419)
Basic refer-
ence
ID105
ID106
107 CURRENT LIMIT (2.5, 2.1.5)
This parameter tells the maximum motor current from the AC drive. The range of values for
the parameter is different for each frame size of the drive. When the current limit is changed
the stall current limit (ID710) is internally calculated to 90% of current limit.
When the current limit is active, the drive output frequency decreases.
NOTE!
The Current Limit is not an overcurrent trip limit.
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
0
1
0
Preset speed 2 (DIN5/ID420)
0
0
1
VACON · 235