VACON · 52
Table 16: Input signals, G2.2
Index
Parameter
P2.2.15
Place B Start/Stop
***
logic selection
Place A Reference
P2.2.16
scaling minimum
value
3
Min
Max
Unit
0
6
0.00
320.00
Hz
LOCAL/REMOTE CONTROL APPLICATION
Default
Cust
ID
0
363
0.00
303
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Description
Logic = 0
Ctrl sgn 1 = Start
forward
Ctrl sgn 2 = Start
reverse
Logic = 1
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Run
enable
Logic = 3
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Stop
pulse
Logic = 4
Ctrl sgn 1 = Forward
pulse (edge)
Ctrl sgn 2 = Reverse
pulse (edge)
Logic = 5
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Reverse
pulse
Logic = 6
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Enable
pulse
Selects the fre-
quency that corre-
sponds to the min.
reference signal.