VACON · 324
709 STALL PROTECTION 234567 (2.7.13)
Table 171: Selections for parameter ID709
Selection
number
0
No response
1
Warning
Fault, stop mode after fault
2
according to ID506
Fault, stop mode after fault
3
always by coasting
Setting the parameter to 0 will deactivate the protection and reset the stall time counter. See
Chapter 8.5 Parameters of stall protection (IDs 709 to 712).
710 STALL CURRENT LIMIT 234567 (2.7.14)
You can set the value of this parameter between 0.0 and 2*I
current must be higher than this limit. If parameter ID107 Nominal current limit of motor
changes, this parameter is automatically calculated to 90% of the current limit. See Chapter
8.5 Parameters of stall protection (IDs 709 to 712).
NOTE!
The value of the Stall current limit must be below the motor current limit.
Fig. 74: The stall characteristics settings
711 STALL TIME 234567 (2.7.15)
You can set the time limit between 1.0 and 120.0 s.
8
Selection name
PARAMETER DESCRIPTIONS
Description
. For a stall status to occur, the
H