335 ACTUAL VALUE 2 SELECTION 57 (2.2.10, 2.2.1.10)
Table 129: Selections forparameter IDs 334 and 335
Selection
number
0
Not used
1
AI1
2
AI2
3
AI3
4
AI4
Fieldbus
5
Application 5
6
Motor torque
7
Motor speed
8
Motor current
9
Motor power
Encoder frequency (for Actual
10
value 1 only)
336 ACTUAL VALUE 1 MINIMUM SCALE 57 (2.2.11, 2.2.1.11)
Sets the minimum scaling point for Actual value 1. See Fig. 46 Examples of actual value signal
scaling.
337 ACTUAL VALUE 1 MAXIMUM SCALE 57 (2.2.12, 2.2.1.12)
Sets the maximum scaling point for Actual value 1. See Fig. 46 Examples of actual value signal
scaling.
338 ACTUAL VALUE 2 MINIMUM SCALE 57 (2.2.13, 2.2.1.13)
Sets the minimum scaling point for Actual value 2. See Chapter 339 Actual value 2 maximum
scale 57 (2.2.14, 2.2.1.14).
339 ACTUAL VALUE 2 MAXIMUM SCALE 57 (2.2.14, 2.2.1.14)
Sets the maximum scaling point for Actual value 2. See Fig. 46 Examples of actual value signal
scaling.
8
Selection name
(Actualvalue 1: FBProcessDataIN2; Actual value 2: FBPro-
cessDataIN3). See Chapter 8.7 Fieldbus control parameters
(IDs 850 to 859).
PARAMETER DESCRIPTIONS