VACON · 164
Table 68: Analogue output 3 (Control keypad: Menu M2 -> G2.3.7)
Index
Parameter
Analogue output 3
P2.3.7.1 *
signal selection
Analogue output 3
P2.3.7.2
function
Analogue output 3
P2.3.7.3
filter time
Analogue output 3
P2.3.7.4
inversion
Analogue output 3
P2.3.7.5
minimum
Analogue output 3
P2.3.7.6
scale
Analogue output 3
P2.3.7.7
offset
* = Use TTF method to program these parameters.
6
Min
Max
Unit
0.1
E.10
0
15
0.00
10.00
s
0
1
0
1
10
1000
%
-100.00
100.00
%
MULTI-PURPOSE CONTROL APPLICATION
Default
Cust
ID
0.1
478
5
479
1.00
480
0
481
0
482
100
483
0.00
484
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Description
TTF programming
method used. See
Chapter 8.9 "Ter-
minal to function"
(TTF) programming
principle .
See P2.3.5.2
0 = No filtering
0 = Not inverted
1 = Inverted
0 = 0 mA (0 V)
1 = 4 mA (2 V)