Vacon NX series Applications Manual page 246

All in one
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

VACON · 246
135 PRESET SPEED 10 4 (2.1.24)
136 PRESET SPEED 11 4 (2.1.25)
137 PRESET SPEED 12 4 (2.1.26)
138 PRESET SPEED 13 4 (2.1.27)
139 PRESET SPEED 14 4 (2.1.28)
140 PRESET SPEED 15 4 (2.1.29)
To use these preset speeds in the Multi-Step Speed Application (ASFIFF04), parameter ID301
must be given the value 13. In Multi-Step Speed Application (Application 4), digital inputs
DIN4, DIN5 and DIN6 are assigned to Preset Speed functions. The combinations of these
activated inputs select the preset speed reference.
Table 111: Multi-step speed selections with digital inputs DIN3, DIN4, DIN5 and DIN6
Multi-step speed
Speed
P2.1.22 (8)
P2.1.23 (9)
P2.1.24 (10)
P2.1.25 (11)
P2.1.26 (12)
P2.1.27 (13)
P2.1.28 (14)
P2.1.29 (15)
141 AI3 SIGNAL SELECTION * 567 (2.2.38, 2.2.4.1)
Connect the AI3 signal to the analogue input of your choice with this parameter. For more
information, see Chapter 8.9 "Terminal to function" (TTF) programming principle.
NOTE!
If you use an NXP drive and the Multi-Purpose Control Application (Application 6),
you can control AI3 from fieldbus when this input is set the value 0.1.
8
Multi-step speed sel.
sel. 1 (DIN4)
2 (DIN5)
0
1
0
1
0
1
0
1
Multi-step speed sel.
3 (DIN6)
0
0
0
0
1
0
1
0
0
1
0
1
1
1
1
1
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
PARAMETER DESCRIPTIONS
Multi-step speed
sel. 4 (DIN3)
1
1
1
1
1
1
1
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxp seriesNxs series

Table of Contents