VACON · 176
Table 74: NXP drives: PMS Motor control parameters (Control keypad: Menu M2 -> G2.6.24)
Index
Parameter
P2.6.24.1
Motor type
PMSMShaft posi-
P2.6.24.2
tion
Start angle ID
P2.6.24.3
modified
Start Angle ID cur-
P2.6.24.4
rent
Polarity pulse cur-
P2.6.24.5
rent
P2.6.24.6
I/f current
P2.6.24.7
I/f control limit
P2.6.24.8
FluxCurrent Kp
P2.6.24.9
FluxCurrent Time
6
Min
Max
Unit
0
1
0
65535
0
10
0.0
150.0
%
-1.0
200.0
%
0.0
150.0
%
0.0
300.0
%
0
32000
0.0
100.0
ms
MULTI-PURPOSE CONTROL APPLICATION
Default
Cust
ID
0
650
0
649
0
1691
0.0
1756
-1.0
1566
50.0
1693
10.0
1790
500
651
5.0
652
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Description
0 = Induction
Motor
1 = PMS Motor
Low word of
encoder (endat)
angle correspond-
ing to the shaft 0
position.
Shaft angle identi-
fication current
level 1000 =
100.0% of motor
nominal.
Shaft angle identi-
fication polarity
pulse current level
1000 = 100.0% of
motor nominal (0 =
defaults are used,
negative value dis-
ables polarity pul-
ses).
Dc-current level
during the start
positioning,
0-100.0% of nomi-
nal, PMSM.
Second corner
frquency (mixed
current/voltage
mode frequency)
(0-1000) = 0-100%
of MotorNomFreq.