CONTROL KEYPAD
7.3.3

Keypad control menu (M3)

In the Keypad Controls Menu , you can choose the control place, edit the frequency reference and change
the direction of the motor. Enter the submenu level with the Menu button right .
Code
Parameter
P3.1
Control place
R3.2
Keypad reference
P3.3
Direction (on keypad)
R3.4
Stop button
Table 7-2. Keypad control parameters, M3
7.3.3.1

Selection of control place

There are three different places (sources) which the AC drive can be controlled from. For each control
place, a different symbol will appear on the alphanumeric display:
I/O terminals
Keypad (panel)
Fieldbus
Change the control place by entering the edit mode with the Menu button right . The options can then be
browsed through with the Browser buttons . Select the desired control place with the Enter button . See the
diagram on the next page.
STOP
READY
I/Oterm
Keypad control
P1 P4
STOP
READY
I/ Oterm
Control Place
Keypad
Figure 7-6. Selection of control place
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Min
Max
1
3
Par.
Par. 2.1.2
2.1.1
0
1
0
1
Control place
I/ Oterm
Control Place
I/O Remote
Control Place
enter
Keypad
Unit
Default
Cust
1
Hz
0
1
Symbol
I/O term
Keypad
Bus/Comm
READY
STOP
STOP
READY
Keypa d
vacon • 81
ID
Note
1=I/O terminal
125
2=Keypad
3=Fieldbus
0=Forward
123
1=Reverse
0=Limited function of Stop
button
114
1=Stop button always
enabled
STOP
READY
I/ Oterm
Control Place
I/O Remote
7