Vacon NX series Applications Manual page 27

All in one
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

STANDARD APPLICATION
Table 6: Input signals, G2.2
Index
Parameter
P2.2.2
DIN3 function
Analogue input 2
P2.2.3
reference offset
Reference scaling
P2.2.4
minimum value
Reference scaling
P2.2.5
maximum value
Reference inver-
P2.2.6
sion
Reference filter
P2.2.7
time
AI1 signal selec-
P2.2.8 ***
tion
AI2 signal selec-
P2.2.9 ***
tion
** = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0
8
0
1
0.00
320.00
Hz
0.00
320.00
Hz
0
1
0.00
10.00
s
Default
Cust
ID
1
301
1
302
0.00
303
0.00
304
0
305
0.10
306
A1
377
A2
388
VACON · 27
Description
0 = Not used
1 = Ext. fault, closing
cont.
2 = Ext. fault, open-
ing cont.
3 = Run enable
4 = Acc./Dec. time
select.
5 = Force cp. to IO
6 = Force cp. to key-
pad
7 = Force cp. to field-
bus
8 = Reverse
0 = 0-20 mA (0-10 V)
**
1 = 4-20 mA (2-10 V)
**
Selects the fre-
quency that corre-
sponds to the min.
reference signal 0.00
= No scaling
Selects the fre-
quency that corre-
sponds to the max.
reference signal 0.00
= No scaling
0 = Not inverted
1 = Inverted
0 = No filtering
TTF programming
method used. See
8.9 "Terminal to func-
tion" (TTF) program-
ming principle.
TTF programming
method used. See
8.9 "Terminal to func-
tion" (TTF) program-
ming principle.
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxp seriesNxs series

Table of Contents