Technical Data: Fl1F-H12Rca/B12Rca - IDEC SMARTRELAY User Manual

Hide thumbs Also See for SMARTRELAY:
Table of Contents

Advertisement

Technical data
A.6 Technical data: FL1F-H12RCA/B12RCA
A.6

Technical data: FL1F-H12RCA/B12RCA

Power supply
Input voltage
Permissible range
Reverse polarity protection
Permissible mains frequency
Power consumption
24 VAC
24 VDC
Voltage failure buffering
Power loss
24 VAC
24 VDC
Backup of the real-time clock at 25 °C
Accuracy of the real-time clock
Digital inputs
Number
Electrical isolation
Number of high speed inputs
Input frequency
Normal input
High speed input
Max. continuous permissible voltage
Input voltage
Signal 0
Signal 1
Input current at
Signal 0
Signal 1
Delay time at
0 to 1
1 to 0
Line length (unshielded)
Analog inputs
Number
Range
max. Input voltage
Digital outputs
Number
Output type
Electrical isolation
In groups of
292
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FL1F-H12RCA
FL1F-B12RCA
24 VAC/VDC
20.4 VAC to 26.4 VAC
20.4 VDC to 28.8 VDC
- -
47 Hz to 63 Hz
15 mA to 150 mA
15 mA to 130 mA
Typ. 5 ms
0.4 W to 3.6 W
0.4 W to 3.2 W
Typ. 20 days
Typ. ± 2 s/day
8, optional positive voltage or negative voltage
No
0
Max. 4 Hz
- -
26.4 VAC
28.8 VDC
L
< 5 VAC/VDC
> 12 VAC/VDC
< 1.2 mA
> 2.6 mA
Typ. 1.5 ms
Typ. 15 ms
Max. 100 m
- -
- -
- -
4
Relay outputs
Yes
1