IDEC SmartRelay functions
4.4 Special functions list - SF
4.4.9

Stairwell light switch

Short description
An input edge triggers a configurable and retriggerable time. IDEC SmartRelay resets the
output after this time expires. IDEC SmartRelay can optionally output a warning signal to
warn of the impending time expiration.
Symbol in
IDEC SmartRelay
Parameter T, T and T
Note the defaults of the T parameters listed in topic Time response (Page 124).
The actual value of another already-programmed function can provide the off-delay time T,
the pre-warning time T and the pre-warning period T
following functions:
Analog comparator (Page 183) (actual value Ax
Analog trigger (Page 178) (actual value Ax)
Analog amplifier (Page 191) (actual value Ax)
Analog multiplexer (Page 209) (actual value A )
Analog ramp control (Page 212) (actual value A )
Analog Math (Page 224) (actual value A )
PI controller (Page 216) (actual value A )
Up/down counter (Page 168) (actual value Cnt)
Analog filter (Page 229) (actual value A )
Average value (Page 235) (actual value A )
Max/Min (Page 231) (actual value A )
On-delay (Page 132) (current time Ta)
Off-delay (Page 136) (current time Ta)
On-/off-delay (Page 138) (current time Ta)
Retentive on-delay (Page 140) (current time Ta)
Interval time-delay relay/Pulse output (Page 142) (current time Ta)
150
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
iring
Input Trg
Parameter
Output
L
Description
A signal at input Trg (Trigger) triggers the off-delay
time for the stairwell light switch.
T represents the off-delay time of the output (output
signal transition 1 to 0).
T determines the triggering time for the pre-warning.
T
determines the length of the pre-warning signal.
L
Retentivity:
/
No retentivity
R
The status is retentive.
IDEC SmartRelay resets
IDEC SmartRelay outputs a warning signal before this
time expires.
. ou can use the actual values of the
L
Ay)
after the time T expires.