Technical Data: Fl1F-M08C2R2 - IDEC SMARTRELAY User Manual

Hide thumbs Also See for SMARTRELAY:
Table of Contents

Advertisement

Electrical Life
Switching rate
Mechanical
Ohmic load/lamp load
Inductive load
Notice: For volume load such as fluorescent lamps with capacitors, you must consider the
technical data of fluorescent lamp ballasts. If the current exceeds the maximum allowed surge
current, appropriate contactor relays must switch the flourescent lamps.
When you connect inductive load such as magnet or valve, it is recommended that you use
diode for DC power supply and surge absorber for AC power supply to suppress the counter
electromotive force.
A.3

Technical data: FL1F-M08C2R2

Power supply
Input voltage
Permissible range
Permissible mains frequency
Power consumption
Voltage failure buffering
Power loss at
Digital inputs
Number
Electrical isolation
Number of high speed inputs
Input frequency
Max. continuous permissible voltage
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
100 VAC
240 VAC
100 VDC
240 VDC 
100 VAC/VDC
240 VAC/VDC
100 VAC
240 VAC
100 VDC
240 VDC 
Normal input
High speed input
A.3 Technical data: FL1F-M08C2R2
FL1F-B12RCC
100,000 operations minimum
(rated resistive load,
1800 operations / hour)
10 Hz
2 Hz
0.5 Hz
FL1F-M08C2R2
100 VAC/VDC to 240 VAC/VDC
85 VAC to 265 VAC
100 VDC to 253 VDC
47Hz to 63 Hz
10 mA to 30 mA
10 mA to 20 mA
5 mA to 15 mA
5 mA to 10 mA
Typ. 10 ms
Typ. 20 ms
1.1 W to 3.5 W
2.4 W to 4.8 W
0.5 W to 1.8 W
1.2 W to 2.4 W
4
No
0
Max. 4 Hz
- -
265 VAC
253 VDC
Technical data
FL1F-H12RCC
100,000 operations minimum
(rated resistive load,
1800 operations / hour)
10 Hz
2 Hz
0.5 Hz
287

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents