Control of a digital input
Continuous current I
Surge current
Incandescent lamp load
(25000 switching cycles) at
Fluorescent tubes with ballast
(25000 switching cycles)
Fluorescent tubes, conventionally
compensated (25000 switching cycles)
Fluorescent tubes, uncompensated
(25000 switching cycles)
Derating
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Parallel output circuits for power increase
Protection of output relay
(if desired)
Switching rate
Mechanical
Ohmic load/lamp load
Inductive load
Notice: For fluorescent lamps with capacitors, you must consider the technical data of
fluorescent lamp ballasts. If the current exceeds the maximum allowed surge current,
appropriate contactor relays must switch the flourescent lamps.
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FL1F-H12RCA
FL1F-B12RCA
Yes
Recommended range of application ≥ 100 mA at
th
12 VAC/VDC
Max. 10 A per relay
Max. 30 A
1000 W
10 x 58 W
1 x 58 W
10 x 58 W
None; across the entire temperature range
Power protection B16, 600 A
Power protection B16, 900 A
Not permitted
Max. 16 A,
characteristic B16
10 Hz
2 Hz
0.5 Hz
A.6 Technical data: FL1F-H12RCA/B12RCA
Technical data
293