Technical data
A.2 Technical data: FL1F-B12RCC/H12RCC
Delay time at 0 to 1:
•
•
•
•
Delay time at 1 to 0:
•
•
•
•
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
Dielectric Strength
(between power/input terminals and
output terminals)
In groups of
Control of a digital input
Continuous current I
Surge current
Incandescent lamp load
(25000 switching cycles) at
•
•
Fluorescent tubes with ballast
(25000 switching cycles)
Fluorescent tubes, conventionally
compensated
(25000 switching cycles)
Fluorescent tubes, uncompensated
(25000 switching cycles)
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Derating
Parallel output circuits for power
increase
Protection of output relay
(if desired)
Initial Contact Resistance
Mechanical Life
286
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
120 VAC
240 VAC
120 VDC
240 VDC
120 VAC
240 VAC
120 VDC
240 VDC
th
230/240 VAC
110/120 VAC
FL1F-B12RCC
•
Typ. 40 ms
•
Typ. 30 ms
•
Typ. 25 ms
•
Typ. 20 ms
•
Typ. 45 ms
•
Typ. 70 ms
•
Typ. 60 ms
•
Typ. 75 ms
max. 100 m
4
Relay outputs
Yes
2,500 V AC, 1minute
500 V DC, 1 minute
1
Yes
Recommended range of
application ≥ 100 mA at
12 VAC/VDC
Max. 10 A per relay
Max. 30 A
•
1000 W
•
500 W
10 x 58 W (at 230/240 VAC)
1 x 58 W (at 230/240 VAC)
10 x 58 W (at 230/240 VAC)
Power protection B16, 600 A
Power protection B16, 900 A
None; across the entire
temperature range
Not permitted
Max. 16 A, characteristic B16
100 mΩ maximum
(at 1A, 24V DC)
10,000,000 operations
minimum (no load, 10 Hz)
FL1F-H12RCC
•
Typ. 40 ms
•
Typ. 30 ms
•
Typ. 25 ms
•
Typ. 20 ms
•
Typ. 45 ms
•
Typ. 70 ms
•
Typ. 60 ms
•
Typ. 75 ms
max. 100 m
4
Relay outputs
Yes
2,500 V AC, 1minute
500 V DC, 1 minute
1
Yes
Recommended range of
application ≥ 100 mA at
12 VAC/VDC
Max. 10 A per relay
Max. 30 A
•
1000 W
•
500 W
10 x 58 W (at 230/240 VAC)
1 x 58 W (at 230/240 VAC)
10 x 58 W (at 230/240 VAC)
Power protection B16, 600 A
Power protection B16, 900 A
None; across the entire
temperature range
Not permitted
Max. 16 A, characteristic B16
100 mΩ maximum
(at 1A, 24V DC)
10,000,000 operations
minimum (no load, 10 Hz)
IDEC SmartRelay Manual