Technical data
A.1 General technical data
Air pressure
Pollutants
Ambient mechanical conditions
Degree of protection
Vibrations:
Shock
Free fall (packaged)
EMC specification
Noise emission
Electrostatic discharge
Electromagnetic fields
HF currents on cables and cable
shielding
Burst pulses
High-energy surge pulse (applies only
to FL1F-B12RCC/H12RCC)
Safety to IEC
Clearance and creepage distance
rating
Insulation strength
Cycle time
Cycle time per function
Startup
Startup time at power-up
FL1F communication
Delay time
284
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Criterion
Tested in accordance with
IEC 60068-2-42
IEC 60068-2-43
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-32
EN 55011
EN 55022
IEC 61000-4-2
Severity 3
IEC 61000-4-3
IEC 61000-4-6
IEC 61000-4-4Severity 3
IEC 61000-4-5Severity 3
IEC 60664, IEC 61131-2,
EN 50178
UL 508
CSA C22.2 No. 142
IEC 61131-2
Values
795 hPa to 1080 hPa
3
3
SO
10 cm
/m
, 21 days
2
3
3
H
S 1 cm
/m
, 21 days
2
IP20 for IDEC SmartRelay Base
Modules, expansion modules,
and the FL1F-RD1 excluding
the TDE front panel
IP65 for FL1F-RD1 front panel
5 Hz to 8.4 Hz
(constant amplitude 3.5 mm)
8.4 Hz to 150 Hz
(constant acceleration 1 g)
18 shocks
(half-sine wave 15 g/11 ms)
0.3 m
Limit class B group 1
Limit class B
8 kV air discharge
6 kV contact discharge
Field strength 1 V/m and 10 V/m
10 V
2 kV (supply and digital signal
lines), 1 kV (analog signal lines)
1 kV (power lines) symmetrical
2 kV (power lines) asymmetrical
Fulfilled
Fulfilled
< 0.1 ms
Typ. 9 s
Max. 100 ms