Connecting The Text Display Power Supply; Connecting Idec Smartrelay Inputs - IDEC SMARTRELAY User Manual

Hide thumbs Also See for SMARTRELAY:
Table of Contents

Advertisement

2.3.2

Connecting the Text Display power supply

ou must connect the FL1F-RD1 to an external power supply that supplies a voltage of
12 VDC or 24 VAC/VDC. Text Display includes a power connector. Connect the power supply
to the power connector then plug the power conncetor to the power supply interface on Text
Display.
Note
IDEC recommends that you protect the Text Display with a 0.5 A safety fuse on the power
supply.
2.3.3

Connecting IDEC SmartRelay inputs

Re uirements
At the inputs you connect sensor elements such as: momentary pushbuttons, switches, light
barriers, daylight control switches etc.
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Ethernet interfaces
Power supply
The power connection is non-polar. If you connect a DC power supply to the Text
Display, you can connect the positive supply wire or negative supply wire to either
pin 1 or pin 2.
Pin 3 must be connected to the ground.
IDEC SmartRelay installation and wiring
2.3
iring IDEC SmartRelay
29

Hide quick links: