Technical Data: Fl1F-M08B1S2 - IDEC SMARTRELAY User Manual

Hide thumbs Also See for SMARTRELAY:
Table of Contents

Advertisement

Technical data
A.5 Technical data: FL1F-M08B1S2
Line length (unshielded)
Analog inputs
Number
Range
Cycle time for analog value generation
Line length (shielded and twisted)
Error limit
Digital outputs
Number
Output type
Electrical isolation
In groups of
Control of a digital input
Output voltage
Output current
Short circuit-proof and overload-proof
Short circuit current limitation
Derating
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Parallel output circuit for power increase
Protection of output relay (if desired)
Switching rate
Mechanical
Electrical
Ohmic load/lamp load
Inductive load
1)
When you switch on FL1F-H12SCD or FL1F-M08B1S2, the CPU sends signal 1 to the digital outputs
for about 50 μs. Take this into account, especially when using devices that react to short pulses.
2)
The maximum switching rate is only dependent on the switching program's cycle time.
A.5

Technical data: FL1F-M08B1S2

Power supply
Input voltage
Permissible range
Reverse polarity protection
Permissible mains frequency
Power consumption from 24 VDC
290
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2)
FL1F-H12SCD
Max. 100 m
4 (I1=AI3, I2=AI4, I7=AI1, I8=AI2)
0 VDC to 10 VDC
Input impedance 72 kΩ
300 ms
Max. 10 m
± 1.5% at FS
4
Transistor,
1)
current-sourcing
No
- -
Yes
≤ Supply voltage
Max. 0.3 A per channel
Yes
Approx. 1 A per channel
None; across the entire temperature range
- -
- -
Not permitted
- -
- -
10 Hz
10 Hz
0.5 Hz
FL1F-M08B1S2
24 VDC
20.4 VDC to 28.8 VDC
Yes
- -
15 mA to 40 mA (no load on digital output)
1.2 A (with max. load on digital output )
IDEC SmartRelay Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents