Technical Data: Fl1E-H12Rca/Fl1E-B12Rca - IDEC FL1E-H12RCA User Manual

Fl1e series. smartrelay
Table of Contents

Advertisement

A.6 Technical data: 
FL1E-H12RCA/FL1E-B12RCA
Power supply
Input voltage
Permissible range
Reverse polarity protection
Permissible mains frequency
Power consumption
• 24 V AC
• 24 V DC
Inrush current
Voltage failure buffering
Power loss
• 24 V AC
• 24 V DC
Backup of the real-time clock at 25 C
Accuracy of the real-time clock
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FL1E-H12RCA
FL1E-B12RCA
24 V AC/DC
20.4 ... 26.4 V AC
20.4 ... 28.8 V DC
not applicable for this module
47 ... 63 Hz
76 ... 182 mA
40 ... 100 mA
2.28 A at 24 V DC
2.48 A at 24 V AC
typ. 5 ms
1.8... 4.4 VA
1.0 ... 2.4 W
typ. 80 hours without battery cartridge
typ. 2 years with battery cartridge
typ. 2 s / day
Technical data
309

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents