IDEC SMARTRELAY User Manual page 303

Hide thumbs Also See for SMARTRELAY:
Table of Contents

Advertisement

Power loss at 24 V
Digital inputs
Number
Electrical isolation
Number of high speed inputs
Input frequency
Max. continuous permissible voltage
Input voltage
Input current at
Delay time at
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
In groups of
Control of a digital input
Output voltage
Output current
Short circuit-proof and overload-proof
Short circuit current limitation
Derating
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Parallel output circuit for power increase
Protection of output relay (if desired)
Switching rate
Mechanical
Electrical
Ohmic load/lamp load
Inductive load
1)
When you switch on FL1F-H12SCD or FL1F-M08B1S2, the CPU sends signal 1 to the digital outputs
for about 50 μs. Take this into account, especially when using devices that react to short pulses.
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Normal input
High speed input
Signal 0
Signal 1
Signal 0
Signal 1
0 to 1
1 to 0
A.5 Technical data: FL1F-M08B1S2
FL1F-M08B1S2
0.4 W to 1.0 W
4
No
0
Max. 4 Hz
- -
28.8 VDC
L+
< 5 VDC
> 12 VDC
< 0.88 mA
> 2.1 mA
Typ. 1.5 ms
Typ. 1.5 ms
Max. 100 m
4
Transistor,
1)
current-sourcing
No
- -
Yes
≤ Supply voltage
Max. 0.3 A per channel
Yes
Approx. 1 A per channel
None; across the entire temperature range
- -
- -
Not permitted
- -
- -
10 Hz
10 Hz
0.5 Hz
Technical data
291

Hide quick links:

Advertisement

Table of Contents
loading