Analog Amplifier - IDEC SMARTRELAY User Manual

Hide thumbs Also See for SMARTRELAY:
Table of Contents

Advertisement

4.4.22

Analog amplifier

Short description
This special function amplifies the value of an analog input and outputs the result at an analog
output.
Symbol in
IDEC SmartRelay
AI1...AI8: 0 V to 10 V corresponds with 0 to 1000 (internal value).
Gain and offset parameters
Please note the information on gain and offset parameters in topic Calculating the gain and
offset of analog values (Page 126).
Parameter p (number of decimals)
Applies only to the A
Functional description
The function fetches the analog signal of input Ax.
This value is multiplied by the value of the A (gain) parameter, and parameter B (offset) is
then added to the product: (Ax gain)
The actual value Ax is output at A .
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
iring
Description
Input Ax
Input Ax is one of the following analog signals:
Parameter
A: gain
Range of values: -10.00 to 10.00
B: zero offset
Range of values: -10,000 to 10,000
p: number of decimals
Range of values: 0, 1, 2, 3
Output A
This special function has an analog output. This
output can only be connected with analog inputs,
analog memory markers, analog outputs or network
analog outputs.
Range of values for A :
-32767 to 32767
value in a message text.
offset
IDEC SmartRelay functions
4.4 Special functions list - SF
AI1 to AI8 ( )
AM1 to AM64
NAI1 to NAI32
A 1 to A 8
NA 1 to NA 16
Block number of a function with analog output
actual value Ax.