4.4.22
Analog amplifier
Short description
This special function amplifies the value of an analog input and outputs the result at an analog
output.
Symbol in
IDEC SmartRelay
AI1...AI8: 0 V to 10 V corresponds with 0 to 1000 (internal value).
Gain and offset parameters
Please note the information on gain and offset parameters in topic Calculating the gain and
offset of analog values (Page 126).
Parameter p (number of decimals)
Applies only to the A
Functional description
The function fetches the analog signal of input Ax.
This value is multiplied by the value of the A (gain) parameter, and parameter B (offset) is
then added to the product: (Ax gain)
The actual value Ax is output at A .
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
iring
Description
Input Ax
Input Ax is one of the following analog signals:
Parameter
A: gain
Range of values: -10.00 to 10.00
B: zero offset
Range of values: -10,000 to 10,000
p: number of decimals
Range of values: 0, 1, 2, 3
Output A
This special function has an analog output. This
output can only be connected with analog inputs,
analog memory markers, analog outputs or network
analog outputs.
Range of values for A :
-32767 to 32767
value in a message text.
offset
IDEC SmartRelay functions
4.4 Special functions list - SF
AI1 to AI8 ( )
AM1 to AM64
NAI1 to NAI32
A 1 to A 8
NA 1 to NA 16
Block number of a function with analog output
actual value Ax.