The updated value PV is used to calculate in the formulas:
If the updated value PV = SP, then the special function
does not change the value of AQ.
Dir = upwards (+) (timing diagram numbers 1. and 3.)
-
If the updated value PV > SP, then the special function
reduces the value of AQ.
-
If the updated value PV < SP, then the special function
increases the value of AQ.
Dir = downwards (-) (timing diagram number 2.)
-
If the updated value PV > SP, then the special function
increases the value of AQ.
-
If the updated value PV < SP, then the special function
reduces the value of AQ.
With a disturbance, AQ continues to increase / decrease
until the updated value PV again corresponds to SP. The
speed with which AQ changes depends on the parameters
KC and TI.
If the input PV exceeds the parameter Max, then the updated
value PV is set to the value of Max. If the PV falls short of the
parameter Min, then the updated value PV is set to the value
of Min.
If the input R is set to 1, then the AQ output is reset. As long
as R is set, the input A/M is disabled.
Sampling time
The sampling time is fixed at 500 ms.
Parameter sets
For more information and application examples with
application-related parameter sets for KC, TI and Dir refer to
the online help for WindLGC.
220
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Updated value PV = (PV•gain) + offset