IDEC FL1E-H12RCA User Manual page 324

Fl1e series. smartrelay
Table of Contents

Advertisement

Technical data
Digital inputs
Number
Electrical isolation
High speed inputs
Input frequency
• Normal input
• High speed input
Input voltage
• Signal 0
• Signal 1
Input current at
• Signal 0
• Signal 1
Delay time at
• 0 to 1
• 1 to 0
Line length (unshielded)
Analog inputs
Number
Range
max. Input voltage
Digital outputs
Number
Output type
Electrical isolation
Dielectric Strength (between power/input
terminals and output terminals)
In groups of
Control of a digital input
Continuous current I
Surge current
Incandescent lamp load 
(25000 switching cycles) at
Fluorescent tubes with ballast 
(25000 switching cycles)
Fluorescent tubes, conventionally
compensated (25000 switching cycles)
310
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
th
FL1E-H12RCA
FL1E-B12RCA
8,
optional P action or N action
No
not applicable for this module
• max. 4 Hz
• not applicable for this module
L
< 5 V AC/DC
> 12 V AC/DC
< 1.0 mA
> 2.5 mA
typ. 1.5 ms
typ. 15 ms
100 m
4
Relay outputs
Yes
2,500 V AC, 1minute
500 V DC, 1 minute
1
Yes
max. 10 A per relay
max. 30 A
1000 W
10 x 58 W
1 x 58 W