Technical data
Input current at
• Signal 0
• Signal 1
• Signal 0
• Signal 1
Delay time at
• 0 to 1 : 120 V AC
: 240 V AC
: 120 V DC
: 240 V DC
• 1 to 0 : 120 V AC
: 240 V AC
: 120 V DC
: 240 V DC
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
Dielectric Strength
(between power/input terminals and
output terminals)
In groups of
Control of a digital input
Continuous current I
Surge current
Incandescent lamp load (25000 switching
cycles) at
• 230/240 V AC
• 100/110 V AC
Fluorescent tubes with ballast (25000
switching cycles)
Fluorescent tubes, conventionally
compensated (25000 switching cycles)
Fluorescent tubes, uncompensated
(25000 switching cycles)
Short circuit–proof cos 1
Short circuit-proof cos 0.5 to 0.7
Derating
Parallel output circuits for power increase Not permitted
Protection of output relay (if desired)
300
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
th
FL1E-H12RCC
FL1E-B12RCC
< 0.03 mA AC
> 0.08 mA AC
< 0.03 mA DC
> 0.12 mA DC
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
100 m
4
Relay outputs
Yes
2,500 V AC, 1minute
500 V DC, 1 minute
1
Yes
max. 10 A per relay
max. 30 A
1000 W
500 W
10 x 58 W (at 230/240 V AC)
1 x 58 W (at 230/240 V AC)
10 x 58 W (at 230/240 V AC)
Power protection B16, 600A
Power protection B16, 900A
none; across the entire temperature range
max. 16 A, characteristic B16