Setting the Par parameter
The gain and offset parameters are used to adapt the
sensors to the relevant application.
View in programming mode:
B3
On =+00000
Off =+00000
Press
B3
A
B
p
Example
In a heating control system, the supply T
temperatures T
sensor at AI2.
A control signal is to be triggered (for example "heater On")
when the difference between the supply and return line
temperatures is greater than 15. The control signal is reset
when the difference is less than 5C.
The process variable of the temperature is to be shown in
parameter assignment mode.
The thermocouples available have the the following
technical data: -30 to +70C, 0 to 10 VDC.
-30 to +70
0
Range of values:
-30 to +70
On threshold = 15
Off threshold = 5
See also Chapter 4.3.6.
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
1+
2
=00.00
=+00000
=0
are to be compared, for example with a
r
Application
C = 0 to 10 V DC
C
C = 100
C
C
IDEC SmartRelay functions
Parameter protection mode
On threshold
Off threshold
Gain
Offset
Decimals in the message text
and return line
v
Internal mapping
0 to 1000
300
Offset = -30
1000
Gain = 100/1000 = 0.1
Threshold = 15
Threshold = 5