IDEC FL1E-H12RCA User Manual page 53

Fl1e series. smartrelay
Table of Contents

Advertisement

FL1B-J2B2
L+
M
Current measurement
The illustration above shows an example of four–wire
current measurement and two–wire voltage measurement.
Connecting a two–wire sensor to the FL1B-J2B2
Wire up the two–wire sensor's connecting wires as follows:
1. Connect the sensor's output to connection U (0 ... 10 V
voltage measurement) or to connection I (0 ... 20 mA
current measurement) of the FL1B-J2B2 module.
2. Connect the plus connector on the sensor to the 24 V
supply voltage (L+).
3. Connect the ground connection of the current output M
(on the right side of the sensor, as shown in the figure
above) to the corresponding M input (M1 or M2) on the
FL1B-J2B2 module.
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
IDEC SmartRelay installation and wiring
L+
M
L+
RUN/STOP
PE
M
L+
I1 M1
U1 I2 M2 U2
Current
Reference
0...20mA
Current
M
Voltage measurement
PE
M
0-10V
PE terminal for
connecting earth and
shielding the analog
measuring cable
Earth
Cable shielding
DIN rail
39