Mounting the Text Display

To prepare the mounting surface for the optional Text
Display and mount it, follow these steps:
1. Cut a 119.5 mm x 78.5 mm hole in the mounting surface.
2. Place the included gasket on the frontplate of the Text
Display.
3. Fit the Text Display into the cutout you made in the
mounting surface.
4. Attach the mounting brackets (included) to the Text
Display.
5. Tighten the mounting screws on the mounting brackets to
0.15...0.2 Nm torque to secure the Text Display.
You can then use the included cable to connect the Text
Display to the IDEC SmartRelay base module up to a
distance of 2.5 meters. You can extend this distance to up to
ten meters by using a standard Sub-D cable together with
the Text Display cable.