Technical Data: Fl1D-K2B2, Fl1D-K2Bm2 - IDEC FL1E-H12RCA User Manual

Fl1e series. smartrelay
Table of Contents

Advertisement

A.11 Technical data: 
FL1D-K2B2, FL1D-K2BM2
Power supply
Input voltage
Permissible range
Power consumption
Voltage failure buffering
Power loss at 24 V
Electrical isolation
Reverse polarity protection
Ground terminal
Analog outputs
Number
Voltage range
Voltage load
Current output
Current load
Resolution
Cycle time for analog output
Electrical isolation
Line length (shielded and
twisted)
Error limit
Short circuit protection
Response at short-circuit
Overload protection
Response at overload
(1) Voltage output: If short-circuit protection or overcurrent protection is activated for a
voltage output, the error limit of the other voltage is not ensured.
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FL1D-K2B2
24 V DC
20.4 ... 28.8 V DC
25 ...50 mA
typ. 5 ms
0.6 ... 1.2 W
No
Yes
for connecting ground
and shielding of the
analog output line.
2
0 ... 10 V DC
>= 5 k
-
-
10 bit, normalized to 0 ...
1000
depending on installation
(typ. 50 ms)
No
10 m
Voltage output:
+/- 2.5 % at full scale
Yes
(1)
Yes
(1)
Technical data
FL1D-K2BM2
24 V DC
20.4 ... 28.8 V DC
35 ...90 mA
typ. 5 ms
0.9 ... 2.2 W
No
Yes
for connecting ground
and shielding of the
analog output line.
2
0 ... 10 V DC
>= 5 k
0/4 ... 20 mA
<= 250 
10 bit, normalized to 0 ...
1000
depending on installation
(typ. 50 ms)
No
10 m
Voltage output:
+/- 2.5 % at full scale
Current output:
+/- 3 % at full scale
Yes
(1)
Yes
(1)