Applications
8.7.1
Requirements for a control system of a service
water pump
•
Service water must be available at all times. In case of
emergency, the control system must automatically switch
over to drinking water supply.
•
When switching over to the drinking water supply, the
ingress of rainwater into the drinking water system must
be prevented.
•
The service water pump may not be switched on if the
reservoir has run low of rainwater (dry-run protection).
8.7.2
Previous solution
The pump and a solenoid valve are controlled by means of a
pressure switch and 3 float switches, which are installed in
the rainwater reservoir. The pump must be switched on
when the pressure level in the boiler drops below minimum.
After the operating pressure is reached, the pump is
switched off again after a tracking time of a few seconds has
expired. The tracking time prevents oscillation of the water
pump if water is drawn off over a longer period of time.
294
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Auxiliary circuit
L1
K3
S3
S1
p<
K2
S4
K1
K2
K3
N
Pump
Tracking
time
S2
K3
S3
K4
Dry-run
Drinking water
protection
supply line
IDEC SmartRelay Manual
K4
Y1