Technical data
A.7 Technical data: FL1B-M08D2R2
Power supply
Input voltage
Permissible range
Reverse polarity protection
Permissible mains frequency
Power consumption
• 24 V AC
• 24 V DC
Voltage failure buffering
Power loss
• 24 V AC
• 24 V DC
Backup of the real-time clock at 25 C
Accuracy of the real-time clock
Digital inputs
Number
Electrical isolation
High speed inputs
Input frequency
• Normal input
• High speed input
Input voltage
• Signal 0
• Signal 1
Input current at
• Signal 0
• Signal 1
Delay time at
• 0 to 1
• 1 to 0
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
Dielectric Strength (between power/input
terminals and output terminals)
In groups of
312
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FL1B-M08D2R2
24 V AC/DC
20.4 ... 26.4 V AC
20.4 ... 28.8 V DC
not applicable for this module
47 ... 63 Hz
120 ... 146 mA
20 ... 75 mA
typ. 5 ms
2.4 ... 4.3 VA
0.4 ... 1.8 W
4, optional P action or N action
No
not applicable for this module
• max. 4 Hz
• not applicable for this module
L
< 5 V AC/DC
> 12 V AC/DC
< 1.0 mA
> 2.5 mA
typ. 1.5 ms
typ. 15 ms
100 m
4
Relay outputs
Yes
2,500 V AC, 1 minute
500 V DC, 1 minute
1