Setting the seven-day time switch
To set the on-/off-times:
1. Move the cursor to one of the Cam parameters of the 
timer (e.g. No1).
2. Press OK. IDEC SmartRelay opens the Cam parameter
assignment screen form. The cursor is positioned on the
weekday.
3. Press
4. Press
time.
5. Set the on-time.
Modify the value at the respective position, using the keys
using the keys
select the value - -:- - 
(- -:- - means: No on-/off-times set).
6. Press
time.
7. Set the off-time (in same way as in step 5).
8. Confirm your entries with OK.
The cursor is now positioned on the No2 parameter (Cam2)
and you can configure a further cam.
Note
For information on timer accuracy, refer to the technical data and to
Chapter 4.3.2.
Seven-day time switch: Example
The output of the seven-day time switch switch is to be set
daily from 06:30 h to 08:00 h. The output should also be set
every Tuesday from 03:10 h to 04:15 h, and on the
weekends from 16:30 h to 23:10 h.
This requires three cams.
Here are the parameter assignment screen forms of the
cams No 1, 2 and 3, based on the timing diagram shown
earlier.
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
and
to select one or several days of the week.
to move the cursor to the first position of the on-
and . Move to the cursor to the various positions,
and . At the first position, you can only
to move the cursor to the first position of the off-
IDEC SmartRelay functions