IDEC FL1E-H12RCA User Manual page 186

Fl1e series. smartrelay
Table of Contents

Advertisement

IDEC SmartRelay functions
Parameter p (number of decimals)
Does not apply to the display of On, Off and Ax values in a
message text.
Does not apply to the comparison of On and Off values! (The
compare function ignores the decimal point.)
Timing diagram
1000
On
Off
Ax
0
Q
Functional description
The function fetches the analog signal at input Ax.
Ax is multiplied by the value of the A (gain) parameter, and
the value at parameter B (offset) is added to product, i.e.
(Ax•gain) + offset = actual value of Ax.
Output Q is set or reset, depending on the set thresholds.
See the calculation rule below.
Calculation rule
 If the On threshold  Off threshold, then:
Q = 1, if the actual value Ax > On
Q = 0, if the actual value Ax  Off.
 If the On threshold < Off threshold, then Q = 1 if
On  actual value Ax < Off.
172
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
IDEC SmartRelay Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents