Analog Math - IDEC FL1E-H12RCA User Manual

Fl1e series. smartrelay
Table of Contents

Advertisement

View in parameter assignment mode:
B1
Min=+00000
Max=+01000
A

4.4.30 Analog math

Short description
The analog math block calculates the value AQ of an
equation formed from the user-defined operands and
operators.
Symbol in IDEC
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
1
= 1.00
Wiring
SmartRelay
Input En
Parameter
Output AQ The output AQ is the result of the
IDEC SmartRelay functions
B1
Press
B =+00000
T =00:04s
Description
A change in the status from 0 to 1 at
input En (Enable) enables the analog
math function block.
V1: First operand value
V2: Second operand value
V3: Third operand value
V4: Fourth operand value
Op1: First operator
Op2: Second operator
Op3: Third operator
Pr1: Priority of first operation
Pr2: Priority of second operation
Pr3: Priority of third operation
:
Qen0
0: Reset value of AQ to 0
when En=0
1: Retain last value of AQ
when En=0
p: Number of decimals
Range of values: 0, 1, 2, 3
equation formed from the operand
values and operators. AQ will be set
to 32767 if a divide by 0 or overflow
occurs, and -32768 if a negative
overflow (underflow) occurs.
2