Control of a digital input
Continuous current I
Surge current
Incandescent lamp load (25000 switching
cycles) at
Fluorescent tubes with ballast (25000
switching cycles)
Fluorescent tubes, conventionally
compensated (25000 switching cycles)
Fluorescent tubes, uncompensated
(25000 switching cycles)
Derating
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Parallel output circuits for power increase Not permitted
Protection of output relay (if desired)
Minimum Switching Load
Initial Contact Resistance
Mechanical Life
Electrical Life
Switching rate
Mechanical
Ohmic load/lamp load
Inductive load
Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp
ballasts must also be considered. If the maximum allowed surge current is exceeded,
fluorescent lamps must be switched with appropriate contactor relays.
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
th
FL1B-M08D2R2
Yes
max. 5 A per relay
max. 30 A
1000 W
10 x 58 W
1 x 58 W
10 x 58 W
none; across the entire temperature range
Power protection B16, 600A
Power protection B16, 900A
max. 16 A, characteristic B16
10 mA, 12 V DC
100 mmaximum (at 1A, 24V DC)
10,000,000 operations minimum
(no load, 10 Hz)
100,000 operations minimum (rated
resistive load, 1800 operations / hour)
10 Hz
2 Hz
0.5 Hz