806f0823-2101ffff • 806f0a07-0301ffff
806f0823-2101ffff
Watchdog Timer interrupt occurred for [WatchdogElementName].
Explanation: The Watchdog Timer has expired. A watchdog interrupt has occurred.
May also be shown as 806f08232101ffff or 0x806f08232101ffff
Severity: Info
Alert Category: System - Other
Serviceable: No
CIM Information: Prefix: PLAT and ID: 0376
SNMP Trap ID:
Automatically notify Support: No
User response: Information only; no action is required.
806f090c-2581ffff
[PhysicalMemoryElementName] on Subsystem [MemoryElementName] Throttled.
Explanation: An implementation has detected Memory has been Throttled.
May also be shown as 806f090c2581ffff or 0x806f090c2581ffff
Severity: Warning
Alert Category: System - Other
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0142
SNMP Trap ID: 22
Automatically notify Support: No
User response: Complete the following steps:
1. Check the IMM event log for any fan, cooling, or power related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
806f0a07-0301ffff
[ProcessorElementName] is operating in a Degraded State.
Explanation: The processor 1 is being throttled due to thermal or power conditions.
May also be shown as 806f0a070301ffff or 0x806f0a070301ffff
Severity: Warning
Alert Category: Warning - CPU
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0038
SNMP Trap ID: 42
Automatically notify Support: No
User response: Check the IMM event log for any fan, cooling, or power related issues.
For a thermal condition:
1. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
2. Make sure that the room temperature is within operating specifications.
For a power condition:
1. If Power Supply Unit is rated 1400 Watt, Make sure it is connected to 220V AC input
710
System x3750 M4 Types 8722 and 8733: Installation and Service Guide